XXX-X-XXXX-XXXX-X/XX/$XX.00 ©20XX IEEE
Condition Assessment of Hydrogenerator Stator Bar
Insulation using Partial Discharge Measurements
Torstein Grav Aakre
Department of Electric Power Engeneering
Norwegian University of Science and
Technology (NTNU)
Trondheim, Norway
torstein.aakre@ntnu.no
Erling Ildstad
Department of Electric Power Engeneering
Norwegian University of Science and
Technology (NTNU)
Trondheim, Norway
Sverre Hvidsten
Department of Electric Power Technology
SINTEF Energy Research
Trondheim, Norway
Abstract—This paper presents results from laboratory
measurements of partial discharge (PD) activity in 50 cm long
samples cut from the mainwall section of old hydrogenerator
stator bars. All stator bars were manufactured in 1976 and
samples were taken after 35 years in service from both the low and
high voltage sections of the generator, as well as non-energized
back-up bars. The PD activity, using a phase resolved (PRPDA)
measuring system, was investigated at different test voltages up to
9.6 kV (1.5 U0), frequencies and temperatures in the range 20-
155 ˚C and 0.1-50 Hz, respectively. The service-aged and the
unaged reference samples showed a clear difference in voltage
frequency dependence. It was, however, not possible to distinguish
between service-aged bars from high and low electric stress. The
observed frequency and temperature dependences are discussed
with respect to theoretical assumptions regarding possible void
degradation and surface conductivity.
Keywords— Hydropower, partial discharges, variable voltage
frequency
I. INTRODUCTION
Condition assessment of hydrogenerator stator bars, based
on detection of changes in partial discharge (PD) activity are
performed either as online or offline measurements. During PD-
testing of installed generators, the temperature varies with the
current load or time after shutdown. It is usually beneficial to
perform offline PD tests at low frequency (0.1 Hz) due to the
large capacitance in the generator windings, keeping the test
equipment small. Although, several standardized test procedures
are available [1-3] it is unclear how PD results obtained at
0.1 Hz relate to results measured at 50 Hz, see e.g. [4, 5].
One example of results from trend analysis of online PD
monitoring is given by Bélec et al. [6]. In case of large change
in PD characteristics, a more detailed examination of the
generator revealed the presence of slot discharges. Based upon
this, it was decided to rewind the generator. In case of
considering and comparing the quality of large number of
generators, statistical analysis of PD measurements are used to
locate the critical generators suggested for further more detailed
investigations [7]. An alternative approach is to use measured
phase resolved PD signatures (PRPDA) to build a database of
possible PD sources, for example Hudon et al. [8].
The main purpose of this paper is to examine
experimentally, how PD features change with applied voltage
frequency and temperature and examine if the variable voltage
frequency PD technique can be used as a diagnostic tool for
stator bars.
II. THEORY REGARDING VOID DISCHARGES
PDs occur when the voltage across voids exceeds its
threshold value and a starting electron is available. This means
that the PD inception voltage strongly depends on void shape,
size and availability of starting electron. Charge is deposited
during a PD, opposing the applied field.
The apparent PD charge qa, which can be measured by an
external circuit, can approximately be expressed as
where b according to the well-known abc equivalent of the test
object is the insulation capacitance in series with the void. It is
assumed that the test object capacitance, a, is much larger than
the void capacitance. ΔU is the voltage change across the void
during the PD occurrence.
In order to consider possible effects of testing at low
frequencies the deposited charge qi is here considered to decay
exponentially
where τ is a time constant given by
where σ is the resulting apparent conductivity and ε the
permittivity.
A statistical time lag influence the voltage ΔU and is more
pronounced at higher frequencies, where a certain delay before
initiation gives a PD at a higher voltage. The influence of
statistical time lag on frequency behavior is e.g. described in the
experimental and numerical work in polycarbonate by Forssén
et al. [9]. Here a statistical time lag in the millisecond range was
used to describe an increase in PD magnitude with applied
voltage frequency.
In case of varying the frequency of the applied voltage, three
different cases may occur:
I. The time constant is much smaller than the voltage half
cycle. Deposited charge decay fast.
This work is founded by the project "Hydrogenerator Stator Winding
Insulation Assessment". The project is supported by The Research Council of
Norway (Project No. 255099/E20), and industrial partners.
ݍ
ୟ
= ⋅ Δ (1)
d ݍ
ሺݐሻ
d ݐ
=−
1
ݍ
(2)
=
ߝ
ߪ
(3)