Research Journal of Applied Sciences, Engineering and Technology 4(23): 5123-5128, 2012
ISSN: 2040-7467
© Maxwell Scientific Organization, 2012
Submitted: April 04, 2012 Accepted: April 25, 2012 Published: December 01, 2012
Corresponding Author: Hamid Radmanesh, Hamid Radmanesh, Electrical Engineering Department, Amirkabir University of
Technology (Tehran Polytechnic), Tehran, Iran, Tel.: (+98-21) 64543335, Fax: (+98-21) 88212072
5123
Improving Transient Recovery voltage of circuit breaker using
Fault Current Limiter
1
Amir Heidary,
2, 3
Hamid Radmanesh,
2
Seyed Hamid Fathi and
1
Hamid Reza Rajabi Khamse
1
Electrical Engineering Department, Islamic Azad University, Zanjan Branch, Zanjan, Iran
2
Electrical Engineering Department, Amirkabir University of Technology (Tehran Polytechnic),
Tehran, Iran
3
Electrical Engineering Department, Islamic Azad University, Takestan Branch, Takestan,
Ghazvin, Iran
Abstract: This study investigates influence of Fault Current Limiter (FCL) on short-circuits current level of
substation bus bar splitter circuit breaker and its TRV. An approach for TRV evaluation is developed and
applied for proposed power system as shown in this study. FCL circuit is connected to the power system in
order to limit TRV. The limiter circuit consists of two equal windings which are turned around unique magnetic
core. One of the windings is connected in series with the power system network and the other is connected to
the network via series capacitor and power electronic switches. During normal operating condition, both
tyristors are in on state and current of the primary and secondary windings are equal. This causes zero
impedance of the limiter. During fault, faults current cause the power electronic switch to turn off which
increases the limiter impedance. By increasing the limiter impedance, amplitude of TRV decreases
substantially. The novel method presented in this study is a cheap and successful scheme.
Keywords: Circuit breaker, fault current limiter, transient recovery voltage
INTRODUCTION
Transient Recovery Voltage (TRV) represents the
transient voltage appearing across the terminals of circuit
breakers, following fault currents interruption. The circuit
breaker interruption capability is limited by both the fault
current and the TRV levels. TRV waveform depends on
various factors as: the fault position (Terminal, Short-line
or Transformer faults), the fault type (3LG, 2LG or 1LG
fault), the parameters of the lines connected to the faulted
bus-bars as (IEC56, 1992) define standard envelopes
based on the requirements concerning TRV main
parameters (Rate-of-Rise and Peak Value). If TRV
waveform exceeds the standard envelope, the breaker may
fail to interrupt the current, as high values of the Rate-of-
Rise or the Peak Value may lead to thermal or dielectric
failure in the breaker quenching chamber. In this study an
approach for TRV computation is developed and the
efficiency of different fault current limiting means (as
substation bus-bars splitting) is evaluated from TRV point
of view. Then, new suggested FCL is used for decreasing
the amplitude of the occurred TRV. Although Circuit
Breakers (CBs) in electric power systems are used to
switch on and off the continuous load current under
normal operation conditions, they are primary designed to
break the short circuit current in case a fault occurs. In
order to successfully break the current, the CB has to
withstand the transient recovery voltage that arises across
its terminals when the previous arc column rapidly loses
conductivity after current zero. Besides the magnitude of
the fault current itself, the TRV waveform is the most
significant information needed for choosing the
appropriate CB for a given application. In particular, the
Rate-of-Rise-of-Recovery-Voltage (RRRV) is the
essential parameter. Although manufacturers know the
RRRV capability of their switchgear, customers often
only have inadequate data about the TRV assigned with
their particular application. Especially, the TRV
waveform associated with power transformer secondary
terminal faults is seldom known by the user with the
necessary accuracy. On the other hand, transformers in
electric systems are one of the most costly apparatus. To
illustrate a typical situation of interest, Fig. 1 shows an
equivalent circuit of the power system at an ungrounded
phase-to-phase fault. As a worst case, the TRV across the
first pole-to-clear of a three-phase CB clearing a terminal
fault current is essentially determined by the transformer
alone (Harner, 1968). Therefore, the source side is
represented by three ideal single-phase voltage sources
connected directly to the primary side (inputs). Because
of the wye-delta configuration chosen for this example,
the neutral of the source side is connected to the neutral
bushing of the transformer and to the tank, both connected
to ground. Harner and Rodriguez (1972) published a
study on TRV associated with transformer secondary
faults (Harner and Rodriguez, 1972). They measured the