Experimental and Numerical Investigations of the Behavior
of Flush End Plate Connections at Elevated Temperatures
Hongxia Yu, Ph.D.
1
; I. W. Burgess
2
; J. B. Davison, Ph.D.
3
; and R. J. Plank
4
Abstract: This paper reports on a set of test results on flush end plate connections at ambient and elevated temperatures. The experiments
aimed to investigate the behavior of connections at the ends of unprotected beams in fire situations, when they may be subjected to
significant tying forces and large rotations at elevated temperatures, as a consequence of high beam deflection. A change in first fracture
mode was observed with increasing temperature as the failing component became the bolts rather than the end plate as the strength of
bolts reduces faster than that of steel in fire. At elevated temperatures, the use of thicker end plates can enhance the peak resistance, but
reduces the rotational capacity of the connection. Finite-element analyses were performed to simulate the tested connections, and gave
predictions very close to the observed behavior of the connections in both the loading and the postpeak resistance phases for all the tests
at high temperatures. Via these simulations, minor cracks in the end plate, which were widely observed during the tests, were found to
have little effect on the overall resistance. Development of the forces in each bolt row showed that, at the peak resistance of the connection
force, their distribution can be far from uniform, which emphasizes the need for the full load-displacement-temperature relationships of
bolt rows in simplified component-based analysis methods.
DOI: 10.1061/ASCEST.1943-541X.0000277
CE Database subject headings: Connections; Fires; Finite element method; Simulation; Failures; Temperature effects.
Author keywords: Flush end plate connection; Fire; Finite-element simulation; Failure.
Introduction
A recent trend in the performance-based design of composite
framed structures has been to fire-protect composite beams on the
main column grid, while leaving other beams unprotected. The
unprotected composite beams tend to deflect greatly and may de-
velop some catenary action at very high temperatures. This re-
quires the connections at the beam ends to be able to resist
significant tying forces. Simultaneously, large deflection of the
beam causes the connections to rotate; connections then must
either have high capacity in both rotation and separation to ac-
commodate the deformation, or be very strong in order to force
the rotation into a hogging curvature of the beam end. Therefore,
depending on the type of connection adopted, various levels of
moment may be transferred through it to the supporting member.
Flush end plate connections are widely used in construction
practice in the U.K., and their moment-rotation characteristics
have been investigated previously, both at ambient temperature by
Aggarwal 1994 and at elevated temperatures by Al-Jabri et al.
2005. However, calculation of the tying capacity, as specified by
the U.K. design recommendations The Steel Construction Insti-
tute and The British Constructional Steelwork Association Lim-
ited SCI & BCSA 2002, is based on the assumptions:
• That the connection is subjected to pure tension; and
• That each bolt row contributes fully to its total tying
resistance.
This situation is impossible in practice, as the coexistence of
other actions reduces the resistance of individual fasteners. For
the whole connection, all the bolt rows may not reach their maxi-
mum resistance simultaneously unless their behavior is ductile. If
this is not the case an “unzipping” failure may occur as the most
heavily deformed components fail before sufficient redistribution
to less loaded areas is achieved.
From 2005–2008 the University of Sheffield and University of
Manchester conducted a joint research program with the aim of
investigating the tying capacity and ductility of steel connections
at elevated temperatures. Previous tests by Ding 2007 had
shown that connections could be subjected to tying forces up to
1.6 times the magnitude of the coincident shear force at high
temperatures. Various levels of moment may be transferred
through a connection, depending mainly on the connection type.
Hence, the investigation adopted a test setup in which the con-
nections were subjected to combinations of tying and shear
forces. Moments were generated at the connection from the lever
arm of the applied force. In total, four types of connection were
studied; flush end plates, flexible end plates, fin plates, and web
cleats. This paper reports the test results on flush end plate con-
nections. The behavior of the connections at various temperatures,
and subjected to different load combinations, are given. Different
failure modes are described, and their effects on the behavior of
the connections are illustrated.
Finite-element simulations of the tests have also been per-
1
Lecturer, Dept. of Civil Engineering, Tsinghua Univ., China. E-mail:
yuhx@mail.tsinghua.edu.cn
2
Professor, Dept. of Civil and Structural Engineering, Univ. of Shef-
field, U.K. E-mail: ian.burgess@sheffield.ac.uk
3
Senior Lecturer, Dept. of Civil and Structural Engineering, Univ. of
Sheffield, U.K. E-mail: j.davison@sheffield.ac.uk
4
Professor, School of Architecture, Univ. of Sheffield, U.K. E-mail:
r.j.plank@sheffield.ac.uk
Note. This manuscript was submitted on June 1, 2009; approved on
June 30, 2010; published online on July 15, 2010. Discussion period open
until June 1, 2011; separate discussions must be submitted for individual
papers. This paper is part of the Journal of Structural Engineering, Vol.
137, No. 1, January 1, 2011. ©ASCE, ISSN 0733-9445/2011/1-80–87/
$25.00.
80 / JOURNAL OF STRUCTURAL ENGINEERING © ASCE / JANUARY 2011
Downloaded 10 Oct 2011 to 166.111.44.246. Redistribution subject to ASCE license or copyright. Visit http://www.ascelibrary.org