IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 31, NO. 3, JUNE 2016 999
A Three-Terminal Line Protection
Scheme Immune to Power Swing
Paresh Kumar Nayak, Ashok Kumar Pradhan, Senior Member, IEEE, and Prabodh Bajpai, Member, IEEE
Abstract—Communication-assisted distance protection schemes
are widely used for three-terminal line protection and are suscep-
tible to power swings. The available differential protection scheme
is also considered to be suited to protect three-terminal lines and
is free from problems associated with the power swing. However,
the performance of the current differential protection scheme may
be affected if an outfeed condition occurs during an internal fault.
This paper presents a new technique for protecting three-terminal
transmission lines immune to power swing. The technique uses
synchronized voltage and current measurements from three
terminals for calculating voltage at the tee-point. The maximum
magnitude of the superimposed component of positive-sequence
voltage estimated at the tee-point is compared with the maximum
magnitude of superimposed componentas of the positive-sequence
voltage measured at three terminals of the line to discriminate
a fault from power swing. The method is accurate even for an
outfeed condition during the internal fault, current-transformer
saturation during severe internal or external faults, large load
rejection, and different prefault loading conditions occur during
the power swing. The proposed algorithm is verified using data
simulated through EMTDC/PSCAD for a 400-kV double-circuit
three-terminal system.
Index Terms—Communication-assisted distance protection
schemes, differential protection, fault detection, line fault, power
swing, three-terminal lines.
I. INTRODUCTION
M
ULTITERMINAL lines are often used both at the
transmission and subtransmission levels to exploit
economic, technical, and environmental benefits over two-ter-
minal lines. Among different multiterminal configurations,
the most used one is the three-terminal line. The use of the
three-terminal line imposes severe protection challenges to
different protection schemes, including distance relays [1]. The
presence of a third source-terminal causes the distance relay to
underreach for line faults beyond the tap point. The underreach
problem can be overcome by extending the relay reach which
limits the load-carrying capability and increases the possibility
of unwanted operation during stable power swings.
The NERC blackout report [2] points out that most of the
lines that tripped just before the cascade tripping were three-ter-
Manuscript received May 14, 2014; revised September 12, 2014 and
November 15, 2014; accepted December 22, 2014. Date of publication January
13, 2015; date of current version May 20, 2016. Paper no. TPWRD-00553-2014.
P. K. Nayak is with the Department of Electrical Engineering, Indian School
of Mines, Dhanbad 826004, India (e-mail: pareshkumar.nayak@gmail.com).
A. K. Pradhan and P. Bajpai are with the Department of Electrical Engi-
neering, Indian Institute of Technology, Kharagpur 721302, India (e-mail:
akpradhan@ee.iitkgp.ernet.in; pbajpai@ee.iitkgp.ernet.in).
Digital Object Identifier 10.1109/TPWRD.2014.2387873
minal lines. The distance relay also has an overreaching problem
while protecting three-terminal lines during the outfeed condi-
tion. The limitation of stepped-distance relaying for the pro-
tection of the three-terminal line is overcome by using com-
munication-assisted distance protection or the unit protection
scheme [3], which provides 100% protection to such lines. The
communication-assisted distance protection schemes for such
lines are direct underreaching transfer trip (DUTT), permissive
overreaching transfer trip (POTT), and directional comparison
blocking (DCB). Out of these, POTT and DCB schemes are set
with zone-2 coverage for protecting the full line which needs to
be extended to account for the infeed effect. This may cause the
apparent impedance to appear within the protected zone at all
terminals during the stable power swing, resulting in unwanted
protection operation [4]. To enhance the security of operation
during the power swing, the power-swing blocking (PSB) func-
tion is utilized with such schemes to block them from malop-
eration [5]. However, if a fault occurs during the power swing,
it must be detected correctly to unblock the scheme. The detec-
tion of the symmetrical fault during the power swing is a chal-
lenging issue as both phenomena are balanced in nature. Dif-
ferent techniques have been proposed on this issue using local
signals [6]–[10] and are applied to two-terminal lines only.
The current differential scheme is also used for the protection
of three-terminal lines. This scheme has faster response and is
free from problems associated with the power swing [11]–[13].
However, the scheme may fail if the outfeed condition arises
due to an internal fault the during power swing, or CT satura-
tion occurs due to severe external faults in a three-terminal line
during the power swing [4], [14]. Thus, there is a scope for im-
provement in the protection for such lines.
In this paper, a superimposed component of the voltage-based
technique is proposed for three-terminal line protection with a
target to improve the protection function even during the power
swing. The scheme detects a fault in such a line by comparing
the maximum magnitude of the superimposed component of
the positive-sequence estimated voltage at the tee-point with
the maximum magnitude of the superimposed component of the
positive-sequence voltage at three terminals of the line. The pos-
itive-sequence voltage at the tee-point is estimated by using syn-
chronized positive-sequence voltage and current signals from
each end of the three terminals. The performance of the algo-
rithm is evaluated for various fault and nonfault events during
the power swing and is found to be accurate.
II. PROPOSED ALGORITHM
Protective relays, today with global positioning system
(GPS) technology, have synchronized measurement capabilities
0885-8977 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.