EFFECT OF INSULATIONS ON COP IN VAPOR
COMPRESSION REFRIGERATION SYSTEM
Anusha Peyyala
Assistant Professor P V P Siddhartha Institute of Technology, Research Scholar,
Acharya Nagarjuna University, India.
Dr N V V S Sudheer
Associate Professor, R V R & J C College of Engineering, Guntur India
ABSTRACT
In this project, experimentation is done on Vapour Compression Refrigeration
System [VCRS] as the COP is high for this system and it is the present trend of the
HVAC in the domestic industry. This study presents investigation of best suited
refrigerant and insulation combination for gas pipeline and liquid pipeline of a split air
conditioning system. Analysis are performed for R22-Chlorodiflouromethane, a
HydroChloroFlouro Carbon refrigerant, which has been using in the present world that
cause both global warming and ozone layer depletion and R410a, mixture of di-
flouromethane and pentaflouroethane, a Hydroflouro carbon refrigerant, which is
future of HVAC which reduces the effect of ozone layer depletion [ODP] and Global
Warming Potential [GWP].For these two refrigerants, we had found out the best
insulation suitable as insulation also affects the COP of air conditioner, which has been
observed from the literature. Minimizing the temperature of refrigerant in suction line
helps condensing unit work more effectively intern the system performance increases.
This reduces the overall power required for working of air conditioner, thereby
reducing the maintenance cost of system. Also, it helps the manufacturer to provide best
type of insulation for the system at reduced cost thereby reducing overall cost of
VCRS.To perform the experimental comparison, 16 tests were carried out for 5 times
with each refrigerant Insulation combination. From analysis it is observed that, COPA
for NRF+AF gives highest value for R22 and R410awhen compared to various
insulation materials. Power required for VCRS is greater while using R410a than R22.
So In this work the main energy parameters such as COP and work required for
compressor are analysed and discussed.
Key words: Gas Pipeline Insulation; Liquid pipeline Insulation; R22; R410a; ODP;
GWP; VCRS
Cite this Article: Anusha Peyyala and Dr N V V S Sudheer, Effect of Insulations on Cop
in Vapor Compression Refrigeration System, International Journal of Mechanical
Engineering and Technology, 10(01), 2019, pp.1201 1208 –
http://iaeme.com/Home/issue/IJMET?Volume=10&Issue=1