IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, VOL. 49, NO. 2, APRIL 2000 315
Measurement of Harmonic Losses in Transformers
Supplying Nonsinusoidal Load Currents
Lorenzo Peretto, Member, IEEE, Renato Sasdelli, Member, IEEE, and Giovanni Serra, Member, IEEE
Abstract—The spread of the load control techniques based
on power electronics is causing the increase of harmonic losses
in power distribution systems. A digital method for the evalua-
tion of these losses in power transformers, which only requires
measurements taken at the transformer output terminals, is
discussed in this paper. The accuracy of the method, along with
the performance of a virtual-instrumentation-based instrument
implementing it, is also discussed. The results of some experi-
mental work are reported.
Index Terms—Digital measurements, harmonic distortion, non-
linear systems, power transformer losses, testing.
I. INTRODUCTION
I
NDUSTRIAL equipment and household appliances based
on power electronics are aimed at more efficient uses of elec-
tricity. Nevertheless, the ever-increasing use of electric loads
that contain nonlinear and time-varying devices also results in
growing harmonic distortion of the line currents in power distri-
bution systems. The harmonic currents determine the increase of
losses in power apparatus and systems. Owing to this increase,
neutral conductors may need to be resized, and power apparatus,
such as transformers, may need to be derated. Indeed, the current
distortion determines the increase of the following transformer
losses:
• the losses ( being the dc winding resistance), by
increasing the rms value of the load current;
• the winding eddy current losses, which are proportional
to the square of the frequency (both losses can cause ab-
normal winding temperature rise);
• other stray losses in the core, clamps, and other structural
parts.
The traditional metering practices fail to account for these
costs that are therefore shared by all electric energy purchasers.
Investigation methodologies able to provide information about
the impact of new technologies on distribution systems in terms
of harmonic losses are therefore searched for. New test methods
would also be useful to validate the conventional procedures,
such as those endorsed by standards [1], [2], for establishing the
capability of transformers when supplying nonsinusoidal load
currents. A method to measure the transformer losses in oper-
ating conditions was proposed in [3]. It allows obtaining the
total losses as the sum of two powers measured at the trans-
former input and the output terminals, respectively. To reach this
Manuscript received May 26, 1999; revised November 22, 1999.
The authors are with Dipartimento di Ingegneria Elettrica, Università degli
Studi di Bologna, Bologna I-40136 Italy (e-mail: lorenzo.peretto@mail.ing.
unibo.it; renato.sasdelli@mail.ing.unibo.it; giovanni.serra@mail.ing.unibo.it).
Publisher Item Identifier S 0018-9456(00)02439-6.
Fig. 1. (a) Circuit where a distorting load is supplied by a sinusoidal source
and (b) active-power flow in the circuit.
goal, the voltage and current transducers must have the same
nominal ratio, and this must be very close to the transformer
ratio. Moreover, the transducers must feature the same transfer
function in the frequency bandwidth of the signals. Meeting
this requirement can be very difficult in the case of the pri-
mary-voltage transducers.
A method to measure the harmonic losses and their effect on
the efficiency of power transformers is discussed in this paper. It
only requires measurements at the output terminals of the trans-
former under test, so that high-voltage transducers are not neces-
sary. This paper also deals with the performance of a measuring
instrument based on the virtual instrumentation (VI) technique
that implements the method. Finally, the results of some exper-
imental work for the method’s validation are presented.
II. THEORETICAL BACKGROUND
The measurement method recalled here relies on the flow
analysis of the harmonic active powers in circuits supplied by
sinusoidal generators (see [4]). It only requires power measure-
ments at the transformer output terminals; hence it makes un-
necessary the use of high-voltage transducers.
Let us refer to the schematic diagram in Fig. 1(a), where a
load that draws a distorted current
Re (1)
is supplied by a source of sinusoidal electromotive force .
We assume that the Thevenin equivalent impedance of the
source is independent of . Each current component causes a
voltage drop across ; hence, the voltage in
Re (2)
i.e., the voltage applied to the load, is also distorted. In (1) and
(2), is the angular frequency of ; is the complex rms
0018-9456/00$10.00 © 2000 IEEE