JURNAL INOVTEK POLBENG, VOL. 8, NO. 1, JUNI 2018 ISSN 2088-6225 E-ISSN 2580-2798 58 ANALISA PERFORMANSI SAFETY INSTRUMENT SYSTEM (SIS) PADA HRSG PLTGU DI PT. PJB UP GRESIK Anindita Adikaputri Vinaya 1 1 Departemen Manajemen Rekayasa, Universitas Internasional Semen Indonesia E-mail: anindita.vinaya@uisi.ac.id 1 Abstrak Heat Recovery Steam Generator (HRSG) merupakan komponen penting dalam pembangkit energi listrik. Jika HRSG gagal maka PLTGU dapat mengalami kondisi trip atau kondisi mesin mati secara tiba-tiba dan dapat berpengaruh pada pasokan listrik di PLTGU. Heat Recovery Steam Generator (HRSG) tersebut bekerja pada temperatur dan tekanan yang tinggi sehingga membutuhkan tingkat safety yang tinggi untuk menjaga dari kondisi bahaya. Oleh karena itu perlu dilakukan analisa performansi Safety Instrumented system (SIS) atau sistem proteksi pada HRSG, karena SIS berperan untuk memonitor dan melakukan aksi jika terjadi kondisi berbahaya.Untuk mempresentasikan SIS HRSG secara kuantitatif digunakan nilai Safety Integrity Level (SIL) atau level tingkat keamanan. Metode yang digunakan adalah Fault Tree Analysis (FTA). Metode ini digunakan untuk menentukan nilai SIL berdasarkan konstruksi FTA yang sudah ditentukan. Pengambilan data yang digunakan adalah diagram P&ID dan data maintenance tiap komponen yang ada pada HRSG. Kebutuhan performansi Safety Instrumented system HRSG berdasarkan metode risk graph dan standard IEC 61508 yaitu kategori SIL 2 sedangkan Safety Instrumented system kuantitatif dengan metode Fault Tree Analysis (FTA), diperoleh nilai SIL yang tidak termasuk dalam kategori standard IEC 61508 dengan nilai PFD 12,6977, dimana nilai PFD menunjukkan probabilitas terjadinya kegagalan. Berdasarkan diagram FTA HRSG sistem pada exhaust damper menunjang paling besar terhadap munculnya kegagalan pada HRSG, dengan nilai PFD sebesar 1,6089. Sedangkan, untuk komponen yang menunjang paling besar yaitu Limit Switch (LS) pada exhaust damper dengan PFD sebesar 0,7008. Kata Kunci: Safety Instrumented system, Fault Tree Analysis, HRSG Abstract Heat Recovery Steam Generator (HRSG) is an important component in power generation. If HRSG fails then PLTGU can experience the condition of trip or machine condition to die suddenly and can affect the power supply in PLTGU. The Heat Recovery Steam Generator (HRSG) works at high temperatures and pressures requiring a high level of safety to guard against hazards. Therefore it is necessary to perform Safety Instrumented system (SIS) performance analysis or protection system on HRSG, because SIS role to monitor and perform action in case of dangerous condition. To present SIS HRSG quantitatively used Safety Integrity Level (SIL) or level of security level . The method used is Fault Tree Analysis (FTA). This method is used to determine the value of SIL based on a predetermined FTA construction. Data retrieval used is P & ID diagram and maintenance data of each component in HRSG.The performance requirement of HRSG Safety Instrumented system based on risk graph method and IEC 61508 standard is SIL 2 category while Quantitative Safety Instrumented system with Fault Tree Analysis (FTA) method, obtained SIL value not included in IEC 61508 standard category with PFD value 12.6977, Where the PFD value indicates the probability of failure. Based on the HRSG FTA diagram the system on the exhaust damper supports the most on the occurrence of failure on HRSG, with a PFD value of 1.6089. Meanwhile, for the largest supporting components of the Limit Switch (LS) on the exhaust damper with PFD of 0.7008. Keywords : Safety Instrumented system, Fault Tree Analysis, HRSG 1. PENDAHULUAN Pembangkit Listrik Tenaga Gas dan Uap (PLTGU) pada PT. PJB UP Gresik memiliki beberapa komponen utama yaitu gas turbin generator, HRSG, dan steam turbin generator [1]-[2]. Dalam menghasilkan listrik, unit PLTGU dipengaruhi oleh kinerja dari semua komponen-komponen yang terlibat di dalam unit PLTGU tersebut, salah satunya dipengaruhi oleh kinerja dari HRSG. Mesin Heat Recovery Steam Generator (HRSG) yang terdapat di PT. PJB UP Gresik merupakan salah satu mesin utama dalam proses pembangkitan listrik di PLTGU [1]. Dalam proses produksinya HRSG memiliki peran penting dengan memanfaatkan gas buang dari PLTG untuk memproduksi uap yang digunakan sebagai fluida kerja di PLTU. Pada umumnya HRSG terdiri dari beberapa seksi- seksi yaitu pemanas awal kondensat (kondensat preheater), ekonomiser, evaporator dan superheater [2].