Contents lists available at ScienceDirect
Electrical Power and Energy Systems
journal homepage: www.elsevier.com/locate/ijepes
An improved method for harmonic mitigation and stability improvement of
the grid-connected inverters under local load variation and weak grid
condition
Elham Samavati, Hamid Reza Mohammadi
⁎
Faculty of Electrical and Computer Engineering, University of Kashan, Kashan, Iran
ARTICLE INFO
Keywords:
Variable virtual admittance (VVA)
Grid-connected inverter
Variable grid impedance
Impedance-based stability criterion
Variable local load
ABSTRACT
Variable voltage and current harmonics appear to be critical challenges for grid-connected inverters at the point
of common coupling (PCC). The nonlinear local load and grid impedance variations contribute a lot to the
problem. In this paper, a novel control strategy is proposed using the variable virtual admittance (VVA) and
series active filter concepts capable of improving harmonic mitigation and stability in grid-connected inverters.
The magnitude and phase angle of the VVA are adaptively determined according to the local load variation.
Moreover, the series active filter injects a series voltage to reduce the grid impedance effect. The proposed
control method can be simply implemented, where sinusoidal grid-injected current and sinusoidal local load
voltage can also be achieved under local load variation and weak grid condition. The theoretical approach is
verified using several simulation case studies in Matlab/Simulink software.
1. Introduction
The increasing application of renewable energy sources in power
system has imposed extensive changes in transmission and distribution
levels. Recent widespread application of nonlinear local loads and the
grid voltage harmonics have led to increased grid-injected current
harmonics in the Distributed Generation (DG) systems. The harmonic
pollution however, is deteriorated in cases of nonlinear local load and
grid impedance variations. This problem can be solved by designing
appropriate power quality compensators [1]. The grid-connected in-
verters should be controlled in such a way that the grid-injected current
has the minimum harmonic content [2,3]. The IEEE 1547 standard
determined the allowable limits for both voltage and grid-injected
current harmonics at the point of common coupling (PCC). If the Total
Harmonic Distortion (THD) of the PCC voltage exceeds its limit, then
the THD of the grid-injected current is increased excessively. Conse-
quently, the protective system operates and disconnects the DG unit
from the grid [4,5]. The major challenge is hence related to the effect of
the grid impedance and nonlinear local load variations, where har-
monic instability of the DG unit occurs due to the deteriorated har-
monic pollution. On the other hand, it is worth noting that resonant
frequency variation is caused by the grid impedance variation. In such
conditions, the grid-connected inverter remains stable if the ratio of the
equivalent grid impedance to the inverter output impedance satisfies
the Nyquist stability criterion [6]. In recent years, several control
methods have been introduced aiming to suppress harmonic dis-
turbances at the PCC using: multi-loop Proportional Resonant (PR)
controllers [7], grid voltage feedforward control [8,9],
∞
H repetitive
controller [10,11], employing an auxiliary inverter [12,13], control
techniques based on virtual impedance [14–25], and inverter output
impedance shaping methods [26–29]. Moreover, to address the re-
sonant problem and achieve better harmonic rejection, the active
damping control loop using capacitor current feedback was employed,
leading to improved stability of the control system [30,31].
In a study [12], an auxiliary inverter containing a series LC filter
was used, where by adjusting the parameters of the series LC filter, the
main inverter output impedance was increased leading to harmonic
suppression at the PCC. In another study [13], two parallel inverters
were employed for simultaneous harmonic compensation of the PCC
voltage and grid-injected current. The first inverter reduced the har-
monics of the local load voltage, while the second one reduced the
current harmonics produced by the nonlinear local load. Additionally,
in a number of studies [14–18], virtual impedance was applied in series
with the grid to reduce the voltage harmonics at the PCC. Harmonic
voltage references were also generated in other works [19–21] based on
harmonic virtual resistance and inductance in positive and negative
sequences. Load voltage harmonics were suppressed by adaptive virtual
impedance elsewhere [22], where the magnitude of virtual impedance
https://doi.org/10.1016/j.ijepes.2020.106310
Received 9 December 2019; Received in revised form 12 June 2020; Accepted 16 June 2020
⁎
Corresponding author at: Faculty of Electrical and Computer Engineering, University of Kashan, Ravand Blvd., P.O. Box 8731753153, Kashan, Iran.
E-mail address: mohammadi@kashanu.ac.ir (H.R. Mohammadi).
Electrical Power and Energy Systems 123 (2020) 106310
0142-0615/ © 2020 Elsevier Ltd. All rights reserved.
T