International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 07 | July 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 2732
SHORT CIRCUIT ANALYSIS OF ELECTRICAL DISTRIBUTION SYSTEM FOR
INDUSTRY APPLICATION USING ETAP SOFTWARE
Manu K S
1
, Dr. C Santhana Lakshmi
2
, Dr. S Purushotham
3
, Dr. V Shanmugasundaram
4
,
Dr. R Satheesh
5
1
Manu K S: Student, Dept. of EEE, SCT, Salem, Tamil Nadu, India
2
Dr. C. Santhana Lakshmi (co-author): Assist Professor (Sr Gd) Dept. of EEE, SCT, Salem, Tamil Nadu, India
3
Dr. S. Purushotham (co-author): Assist Professor, Dept. of EEE, SCT, Salem, Tamil Nadu, India
4
Dr.V. Shanmugasundaram (co-author): Assist Professor, Dept. of EEE, SCT, Salem, Tamil Nadu, India
5
Dr. R Satheesh (co-author): Assist Professor, Dept. of EEE, SCT, Salem, Tamil Nadu, India
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - An in-depth analysis of short circuits in power
distribution systems for industry is presented. A power
system short circuit study is performed to ensure the
completeness of the equipment fault classification and to
provide specifications for newly installed equipment to
withstand the degree of short circuit that exists at each
point in the system. Electrical systems Short circuit analysis
helps ensure that personnel and equipment are protected,
by establishing proper tripping ratings of the switches
(breakers and fuses). If the extent of the system failure
exceeds the interrupting capacity of the fault clearing
device, the consequences can be severe. It can seriously
threaten human life and cause personal injury, major
property damage, fire, and costly downtime. In addition, the
short circuit current obtained from the short circuit study is
used for the relay coordination study.
Key Words: Short circuit, Analysis, Industrial distribution
system, Electrical power system study, Industry.
1. INTRODUCTION
A short circuit study is performed to determine the
magnitude of the potential current flowing in the power
system at different time intervals after the fault has
occurred. The amplitude of the current flowing in the
power system after a fault differs with time until they reach
equilibrium. The behavior is due to the characteristics and
dynamics of the system. During this time, a protection
system is required to detect, interrupt and isolate these
faults. The duty for the equipment depends on the
magnitude of the current, which depends on the time since
the onset of the fault. This is done for different fault types
(three-phase, phase-to-phase, two-phase-earth and phase-
to-earth) at different locations in the system. The
information is used to select fuses, circuit breakers and
switchgear sizes in addition to protective relay settings.
Even the best designed electrical systems sometimes
experience short circuits resulting in abnormally high
currents. Overcurrent protective devices, such as circuit
breakers and fuses, must safely isolate the fault from a
provided location with less damage to the circuit and
equipment as well as less interference. for plant working
procedures. Other system devices like cables, busbars and
disconnecting switches, must be able to withstand the
maximum mechanical and thermal stress caused due to the
maximum short-circuit current flowing through those
devices. The amperage of the short-circuit current is
usually estimated by calculation, and the equipment is
selected using the results of the calculation.
The current during a short circuit at any point in the
system is limited by the impedance of the circuit and the
source equipment or sources at the fault point. It is not
directly related to the size of the load on the system.
However, additions to the system to increase the ability
to handle growing loads, such as a larger or larger
transformer from a utility, without affecting the normal
load in some locations. Existing places within the system
can crucially increase the short-circuit current at these
points. When an existing system is expanded or a new
system is installed, the existing short-circuit current must
be determined in order to apply the appropriate
overcurrent protection devices.
The calculated maximum short-circuit current is almost
always required. In some cases, minimum holding values
are also necessary to verify the sensitivity requirements of
current sensitive protective devices.
The scale and complexity of many modern industrial
systems can make long-term short-circuit current
calculations impractical. Calculators are often used for
large short circuit studies.
1.1 Characteristics of Short-Circuit Currents
Full calculation of the short circuit currents will give the
currents as a function of time at the position of the short
circuit from the beginning of the short-circuit until its
termination, corresponding to the instantaneous value of
the voltage at the beginning time of short-circuit currents.