Contents lists available at ScienceDirect
Electric Power Systems Research
journal homepage: www.elsevier.com/locate/epsr
Enhanced grid frequency support by means of HVDC-based load control
☆
Marius Langwasser
⁎
,a
, Giovanni De Carne
a
, Marco Liserre
a
, Matthias Biskoping
b
a
Chair of Power Electronics, Kiel University, Kiel, Germany
b
ABB Research Center Ladenburg, ABB AG, Ladenburg, Germany
ARTICLE INFO
Keywords:
Frequency support
Load sensitivity
Multi-terminal hvdc
Primary frequency regulation
Voltage-dependent loads
ABSTRACT
The two major frequency incidents in Continental Europe and UK call for faster frequency regulation. Hvdc
systems can dynamically adjust the power output to support the frequency regulation by means of droop
characteristics. Adding derivative terms in the power controller enables inertia emulation that improves the
system initial response. As drawback, due to the fast power transfer variation, the HVDC-connected areas suffer
from temporary power imbalance and hence frequency deviation. To overcome this limitation, HVDC-based load
controllers can be implemented at HVDC terminals to shape the consumption of nearby voltage-sensitive loads
by means of controlled voltage variations, with the goal to minimize the frequency deviation in the supporting
areas. In multi-terminal systems, the frequency support can be optimally shared among terminals depending on
the load sensitivity. This minimizes the voltage deviation in supporting areas and limits the hvdc reactive power,
while providing the same frequency damping in the faulty area.
1. Introduction
Nowadays, the electric grid is challenged by the continuous re-
placement of conventional generators with renewables ones, which,
due to their power electronics grid interface, do not provide any rota-
tional inertia to the grid. The result are faster and larger frequency
transients, as it can be observed in the two major incidents in 2019 in
Continental Europe [1] and UK [2]. As practical example, Ulbig et al.
[3] has found that the aggregated inertia in the German grid is about
6 s, if conventional generation dominates, and drops to significantly
lower levels of 3–4 s in times of high wind and PV production. Thus, in
case of large grid contingencies (e.g. grid fault or generator/load shut-
down), an increased frequency deviation from the nominal value is
observed, e.g. from original 400 mHz to more than 550 mHz. Con-
ventionally, synchronous generators stabilize the frequency, which, in
the first seconds after the frequency deviation, adapt their power output
proportionally with the observed frequency change. The same fre-
quency support (FS) can be provided by hvdc systems, but with higher
control dynamics. Hvdc systems with primary frequency regulation
adapt their active power reference rapidly following the frequency
disturbance. This strategy is widely employed in point-to-point [4] and
multi-terminal hvdc (mtdc) systems [5–8]. However, methods such as
the one in Chaudhuri et al. [5], have two drawbacks. First, the fre-
quency/power droop controller only increases the faulty system’s
damping and does not contribute to the system inertia. Second, due to
the fast variation in the power transfer, the supporting grids will ex-
perience temporary power imbalance and thus large frequency devia-
tion of up to 500 mHz. As proposed in Rakhshani et al. [9], Zhu et al.
[10], derivative terms in the hvdc power controller virtually add inertia
to the faulty system. To overcome the second limitation, the hvdc
terminals can be equipped with load control [11,12], which makes use
of the voltage-dependent power characteristic of nearby loads (e.g.
industrial aluminum plants or HV substations [13]), shaping their
power output with controlled grid voltage variation in the first seconds
after frequency disturbance. This concept has been already applied in
SVC [14], synchronous condensers or smart transformers [15,16]. Mtdc
systems can enhance the frequency controllability, since they inter-
connect multiple ac areas and allow for improved power flow control.
In this work, an enhanced FS with mtdc systems controlling voltage
dependent loads is proposed. An optimized distribution of the FS is
implemented respecting the estimated load sensitivity in each con-
nected area. This implies that terminals connected to loads with the
highest sensitivity provide the highest share of FS. As consequence, the
control margin for both upward and downward FS is enlarged, since the
https://doi.org/10.1016/j.epsr.2020.106552
Received 4 October 2019; Received in revised form 17 April 2020; Accepted 20 July 2020
☆
The authors gratefully acknowledge funding by the German Federal Ministry of Education and Research (BMBF) within the Kopernikus Project ENSURE “New
ENergy grid StructURes for the German Energiewende” (03SFK1I0 and 03SFK1I0-2).
⁎
Corresponding author.
E-mail addresses: mlan@tf.uni-kiel.de (M. Langwasser), gdc@tf.uni-kiel.de (G. De Carne), ml@tf.uni-kiel.de (M. Liserre),
matthias.biskoping@de.abb.com (M. Biskoping).
Electric Power Systems Research 189 (2020) 106552
Available online 29 July 2020
0378-7796/ © 2020 Elsevier B.V. All rights reserved.
T