Fire Sci. Eng., Vol. 28, No. 1, pp. 37-43, 2014 37 ISSN: 1738-7167 DOI: http://dx.doi.org/10.7731/KIFSE.2014.28.1.037 화재모델링을 위한 정온식 열감지기의 장치물성 측정 박희원·조재호·문선여·박충화·황철홍 † ·김성찬 * ·남동군 ** 대전대학교 소방방재학과, * 경일대학교 소방방재학과, ** 한국소방산업기술원 Measurement of the Device Properties of Fixed Temperature Heat Detectors for the Fire Modeling Hee-Won Park · Jae-Ho Cho · Sun-Yeo Mun · Chung-Hwa Park · Cheol-Hong Hwang † · Sung-Chan Kim * · Dong-Gun Nam ** Dept. of Fire & Disaster Prevention, Daejeon University *Dept. of Fire Safety, Kyungil University **Korea Institute of Fire Industry & Technology (Received December 27, 2013; Revised February 11, 2014; Accepted February 14, 2014) 요 약 성능위주 소방설계(PBD) 의 과정에서 화재 및 피난모델링의 신뢰성을 확보하기 위해서는 화재감지기 모델의 높은 예 측성능이 필수적으로 요구된다. 본 연구의 목적은 대표적인 화재모델인 FDS 에 적용되고 있는 정온식 열감지기의 정확한 작동 개시시간을 예측하기 위한 입력정보를 측정하는 것이다. 이를 위해 화재감지기의 장치특성을 측정할 수 있는 Fire Detector Evaluator (FED) 가 사용되었으며, 국내에서 적용되는 2 개의 써미스터 방식(Thermistor types) 과 1 개의 바이메 탈 방식(Bimetal type) 의 스포트형 정온식 열감지기가 연구대상으로 고려되었다. 화재모델링을 위해 요구되는 감지기의 작동 개시온도 및 반응시간지수(Response Time Index) 가 측정되었으며, 이때 RTI 는 감지기의 설치위치를 고려하여 천장 제트기류(Ceiling jet flow) 와 수직제트기류(Vertical jet flow) 에 대하여 측정되었다. 측정된 장치물성을 이용한 화재모델 링 결과는 실규모 구획화재실험 결과와 비교·검증되었다. 그 결과 수치적으로 예측된 감지기의 작동 개시시간은 실험 결과를 적절히 잘 예측함을 확인하였다. ABSTRACT The high predictive performance of fire detector models is essentially needed to assure the reliability of fire and evacua- tion modeling in the process of Performance-Based fire safety Design (PBD). The main objective of the present study is to measure input information in order to predictive the accurate activation time of fixed temperature heat detectors adopted in Fire Dynamics Simulator (FDS) as a representative fire model. To end this, Fire Detector Evaluator (FDE) which could be measured the device properties of detector was used, and the spot-type fixed temperature heat detectors of two thermistor types and one bimetal type were considered as research objectors. Activation temperature and Response Time Index (RTI) of detectors required for the fire modeling were measured, and then the RTI was measured for ceiling jet flow and vertical jet flow in consideration of the install location of detectors. The results of fire modeling using mea- sured device properties were compared and validated with the experimental results of full-scale compartment fires. It was confirmed that, in result, the numerically predicted activation time of detector showed reasonable agreement with the measured activation time. Keywords : Fixed temperature heat detector, Fire modeling, Fire Dynamics Simulator (FDS) 1. 서론 국내 초고층 건축물의 화재안전성 평가는 공간 내에 주 어진 화재시나리오에 대하여 거주자가 위험한 상태에 도 달하는 시간, 즉 허용피난시간(Available Safe Egress Time, ASET) 을 화재모델링을 통해 예측하고 동일 공간 내에 거주자가 안전한 곳으로 피난하는데 걸리는 시간인 요구피난시간(Required Safe Egress Time, RSET) 을 평가 하는 방식이 적용되고 있다 (1) . 따라서 ASET 이 RSET 에 비해 클수록 화재상황에 보다 안전한 건물로 평가받게 된 † Corresponding Author, E-Mail: chehwang@dju.ac.kr † TEL: +82-42-280-2592, FAX: +82-42-280-2596